GP33 series UPS is designed for large key application system such as data processing center, the host system, manufacturing and telecommunications equipment, medical equipment and design of the system with high reliability. Its high security and high reliability for large key application system provides an important power protection.
Product features
1, the design has high reliability
GP33 series UPS input power and the bypass power separable, UPS has dual power input, which can be respectively two different grid access road UPS to improve the reliability of the output power. Double conversion on-line topology structure design, the output of the UPS for frequency tracking and phase locking, voltage regulator and filter out noise, from pure sine wave power supply, UPS power grid fluctuation interference to the user equipment to provide more perfect protection.
2, high performance battery
By adopting the technology of smart battery management (ABM), so as to prolong the service life of batteries, reduce battery maintenance times. The advanced constant-current charging pressure automatic conversion technology, activate cells, maximum save charging time, extend the service life of the battery.
3, redundancy/increase redundant weaver ability
Insert the weaver module (option) can be realized as many as eight weaver, increase the reliability of the system. System scalability is strong, easy to implement the weaver. More than one weaver can share a set of UPS backup battery. And can realize the weaver and between different power UPS UPS power size automatically assigned. Without a fixed master-slave relationship weaver; In several parallel UPS units, of which the first boot a primarily (Master) of UPS, the other is from (Slave) UPS, master-slave UPS are interchangeable, if a UPS machine fails, the UPS cut off output, then the power load by the rest of the UPS to provide.
4, energy saving and environmental protection design
Using the model can be disassembled type design, easy maintenance and high saving resource, adopting intelligent fan speed regulation is designed, according to the load of UPS power components, environment temperature and real temperature rise, to intelligent fan on/off and speed control, the cooling performance is superior, high energy saving; Adopting circulation control circuit, power saving performance good; Adopt green rectifier and inverter technology, to provide users with clean energy.
Technical specifications and parameters are as follows:
model
GP3310KS
GP3315KS
GP3320KS
GP3330KS
GP3340KS
GP3360KS
GP3380KS
GP33100KS
GP33120KS
GP33160KS
GP33200KS
The rated capacity (VA)
10 kva
15 kva
20 kva
30 kva
40 kva
60 kva
80 kva
100 kva
120 kva
160 kva
200 kva
The input voltage range
285-480 vac + 25% for three-phase four-wire input
The output frequency range
50/60 hz + 5 hz for automatic identification
Output power factor (PF)
> 0.98
Maximum input current
18 a
27 a
37 a
55 a.
72 a
108 a
130 a
160 a
190 a
245 a
310 a
The output voltage
220 vac or 220 vac) plus or minus 1%
The output frequency
Input frequency automatic tracking
Output waveform
Sine wave
The power factor
0.8
Overload capacity
When 110% / 125% / 150% overload can maintain 300 min / 10 min / 1 min
Protection function
Electronic short circuit current limiting protection for 1.3 times the rated current
Conversion time
0 ms
The battery voltage
384 VDC / 360 VDC / 408 VDC is optional
432 VDC
480 VDC
The LED
Input, inverter, bypass, battery status
The LCD
According to the input and output voltage, frequency, temperature of the battery voltage, load percentage, machine
Waveform distortion
Linear load 3% or less, nonlinear load 5% or less
Operating temperature
0 to 40 ℃
Relative humidity
0-95% no condensation
Storage temperature
25 ℃ to 55 ℃
The noise
The < 54 db
The < 60 db
< 65 db
< 70 db
Net weight (kg)
200
220
240
269
351
497
556
756
901
1300
1350
Gross weight (kg)
256
265
288
305
408
574
633
856
1001
1400
1450
Size (W * D * H) mm
390 * 730 * 1220
550 * 730 * 1220
800 * 730 * 1400
1070 * 745 * 1400
1420 * 745 * 1810